WireSizing
Wire gauge reference & calculator

Flexible Metal (FMC) Conduit Fill Chart

Maximum number of THHN/THWN-2 conductors in Flexible Metal (FMC) (Flexible Metal Conduit (FMC)), trade sizes 3/8 inch through 4 inch. Internal areas from NEC Chapter 9, Table 4; fill limits from Table 1 (53% for one conductor, 31% for two, 40% for three or more). NEC Article 348.

Trade size 40% area (in²) 14121086421/02/04/0
3/8"0.04643111—————
1/2"0.12713963111———
3/4"0.213221610642111—
1"0.3273324159643111
1-1/4"0.511523824141064211
1-1/2"0.743765635201496431
2"1.308135986235251611764
2-1/2"1.96420214793533824171096
3"2.8282912121347755342415128
3-1/2"3.848396289182105764633201712
4"5.026518378238137996143272215

Column headings are AWG conductor sizes, all THHN/THWN-2. A dash means the conductor does not fit even as a single conductor at the 53% limit.

About Flexible Metal (FMC) (Flexible Metal Conduit (FMC))

Spiral-wound interlocked steel or aluminum “Greenfield”. Used for short whips to motors, fixtures and equipment that vibrates or needs to move.

Flexible Metal (FMC) Fill by Trade Size

3/8" Flexible Metal (FMC)
3 × 12 AWG THHN · 0.046 in² usable
1/2" Flexible Metal (FMC)
9 × 12 AWG THHN · 0.127 in² usable
3/4" Flexible Metal (FMC)
16 × 12 AWG THHN · 0.213 in² usable
1" Flexible Metal (FMC)
24 × 12 AWG THHN · 0.327 in² usable
1-1/4" Flexible Metal (FMC)
38 × 12 AWG THHN · 0.511 in² usable
1-1/2" Flexible Metal (FMC)
56 × 12 AWG THHN · 0.743 in² usable
2" Flexible Metal (FMC)
98 × 12 AWG THHN · 1.308 in² usable
2-1/2" Flexible Metal (FMC)
147 × 12 AWG THHN · 1.964 in² usable
3" Flexible Metal (FMC)
212 × 12 AWG THHN · 2.828 in² usable
3-1/2" Flexible Metal (FMC)
289 × 12 AWG THHN · 3.848 in² usable
4" Flexible Metal (FMC)
378 × 12 AWG THHN · 5.026 in² usable

Other Conduit Types

EMT Fill Chart
NEC Article 358
PVC Schedule 40 Fill Chart
NEC Article 352
PVC Schedule 80 Fill Chart
NEC Article 352
Rigid Metal (RMC) Fill Chart
NEC Article 344
IMC Fill Chart
NEC Article 342
Liquidtight (LFMC) Fill Chart
NEC Article 350
ENT Fill Chart
NEC Article 362

Related