3/8" Flexible Metal (FMC) Conduit Fill Chart

14 AWG THHN
4
conductors max
12 AWG THHN
3
conductors max
10 AWG THHN
1
conductors max
Usable area at 40% fill: 0.046 in² · NEC Chapter 9, Tables 1, 4 and 5

About Flexible Metal (FMC) (Flexible Metal Conduit (FMC))

Spiral-wound interlocked steel or aluminum “Greenfield”. Used for short whips to motors, fixtures and equipment that vibrates or needs to move. Trade size 3/8" is covered by NEC Article 348, and its internal dimensions come from NEC Chapter 9, Table 4.

3/8" Flexible Metal (FMC) — Internal Area & Fill Limits

Trade size3/8"
Total internal area (100%)0.116 in²
1 conductor (53%)0.061 in²
2 conductors (31%)0.036 in²
Over 2 conductors (40%)0.046 in²

3/8" Flexible Metal (FMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.00974
120.01333
100.02111
80.03661
60.05071
40.0824—
30.0973—
20.1158—
10.1562—
1/00.1855—
2/00.2223—
3/00.2679—
4/00.3237—
250 kcmil0.3970—
300 kcmil0.4608—
350 kcmil0.5242—
400 kcmil0.5863—
500 kcmil0.7073—
600 kcmil0.8676—
700 kcmil0.9887—
750 kcmil1.0496—
800 kcmil1.1085—
900 kcmil1.2311—
1000 kcmil1.3478—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

3/8" Flexible Metal (FMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.01393
120.01811
100.02431
80.04371
60.05901
40.0814—
30.0962—
20.1146—
10.1534—
1/00.1825—
2/00.2190—
3/00.2642—
4/00.3197—
250 kcmil0.3904—
300 kcmil0.4536—
350 kcmil0.5166—
400 kcmil0.5782—
500 kcmil0.6984—
600 kcmil0.8709—
700 kcmil0.9923—
750 kcmil1.0532—
800 kcmil1.1122—
900 kcmil1.2351—
1000 kcmil1.3519—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 3/8" Flexible Metal (FMC) with 12 AWG THHN: 0.116 × 0.40 ÷ 0.0133 = 3.49 → 3 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 3/8" Flexible Metal (FMC) that raises the usable area from 0.046 in² to 0.07 in².

Other Flexible Metal (FMC) Sizes

3/8" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 3/8-inch Flexible Metal Conduit conduit?

A 3/8-inch Flexible Metal Conduit conduit has 0.116 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.046 in². That works out to 3 #12 THHN, 4 #14 THHN, 1 #10 THHN, or 1 #8 THHN conductors.

How many 12 AWG THHN wires fit in 3/8-inch Flexible Metal Conduit?

3 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 3/8-inch Flexible Metal Conduit is 0.046 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.