3/4" EMT Conduit Fill Chart

14 AWG THHN
21
conductors max
12 AWG THHN
16
conductors max
10 AWG THHN
10
conductors max
Usable area at 40% fill: 0.213 in² · NEC Chapter 9, Tables 1, 4 and 5

About EMT (Electrical Metallic Tubing)

Thin-wall steel tubing, the most common raceway in commercial interiors and exposed residential work. Joined with set-screw or compression couplings, never threaded. Trade size 3/4" is covered by NEC Article 358, and its internal dimensions come from NEC Chapter 9, Table 4.

3/4" EMT — Internal Area & Fill Limits

Trade size3/4"
Total internal area (100%)0.533 in²
1 conductor (53%)0.283 in²
2 conductors (31%)0.165 in²
Over 2 conductors (40%)0.213 in²

3/4" EMT — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009721
120.013316
100.021110
80.03665
60.05074
40.08242
30.09731
20.11581
10.15621
1/00.18551
2/00.22231
3/00.26791
4/00.3237
250 kcmil0.3970
300 kcmil0.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

3/4" EMT — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013915
120.018111
100.02438
80.04374
60.05903
40.08142
30.09621
20.11461
10.15341
1/00.18251
2/00.21901
3/00.26421
4/00.3197
250 kcmil0.3904
350 kcmil0.5153
500 kcmil0.6984
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 3/4" EMT with 12 AWG THHN: floor( 0.533 × 0.40 ÷ 0.0133 ) = 16 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 3/4" EMT that raises the usable area from 0.213 in² to 0.320 in².

Other EMT Sizes

3/4" in Other Conduit Types

Related

Conduit fill calculator → All conduit fill charts → THHN / THWN wire specifications → NEC Table 310.15 derating factors → Ampacity tables →