3-1/2" Rigid (RMC) Conduit Fill Chart

14 AWG THHN
412
conductors max
12 AWG THHN
301
conductors max
10 AWG THHN
189
conductors max
Usable area at 40% fill: 4.004 in² · NEC Chapter 9, Tables 1, 4 and 5

About Rigid Metal Conduit (RMC)

Heavy-wall threaded steel conduit — the thickest and strongest raceway in the NEC. Used for service masts, hazardous locations, and anywhere physical damage is likely. Trade size 3-1/2" is covered by NEC Article 344, and its internal dimensions come from NEC Chapter 9, Table 4.

3-1/2" Rigid (RMC) — Internal Area & Fill Limits

Trade size3-1/2"
Total internal area (100%)10.010 in²
1 conductor (53%)5.305 in²
2 conductors (31%)3.103 in²
Over 2 conductors (40%)4.004 in²

3-1/2" Rigid (RMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097412
120.0133301
100.0211189
80.0366109
60.050778
40.082448
30.097341
20.115834
10.156225
1/00.185521
2/00.222318
3/00.267914
4/00.323712
250 kcmil0.397010
300 kcmil0.46088
350 kcmil0.52427
400 kcmil0.58636
500 kcmil0.70735
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

3-1/2" Rigid (RMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139288
120.0181221
100.0243164
80.043791
60.059067
40.081449
30.096241
20.114634
10.153426
1/00.182521
2/00.219018
3/00.264215
4/00.319712
250 kcmil0.390410
350 kcmil0.51537
500 kcmil0.69845
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 3-1/2" Rigid (RMC) with 12 AWG THHN: floor( 10.010 × 0.40 ÷ 0.0133 ) = 301 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 3-1/2" Rigid (RMC) that raises the usable area from 4.004 in² to 6.006 in².