5" PVC Schedule 80 Conduit Fill Chart

14 AWG THHN
736
conductors max
12 AWG THHN
537
conductors max
10 AWG THHN
338
conductors max
Usable area at 40% fill: 7.142 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Schedule 80 (Rigid PVC Conduit, Schedule 80)

Heavy-wall PVC required where conduit is exposed to physical damage, such as risers on poles and service masts. Same outside diameter as Schedule 40, so the thicker wall takes noticeably more room from the inside. Trade size 5" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

5" PVC Schedule 80 — Internal Area & Fill Limits

Trade size5"
Total internal area (100%)17.855 in²
1 conductor (53%)9.463 in²
2 conductors (31%)5.535 in²
Over 2 conductors (40%)7.142 in²

5" PVC Schedule 80 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097736
120.0133537
100.0211338
80.0366195
60.0507141
40.082486
30.097373
20.115861
10.156245
1/00.185538
2/00.222332
3/00.267926
4/00.323722
250 kcmil0.397018
300 kcmil0.460815
350 kcmil0.524213
400 kcmil0.586312
500 kcmil0.707310
600 kcmil0.86768
700 kcmil0.98877
750 kcmil1.04967
800 kcmil1.10856
900 kcmil1.23116
1000 kcmil1.34785
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

5" PVC Schedule 80 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139514
120.0181394
100.0243294
80.0437163
60.0590121
40.081487
30.096274
20.114662
10.153446
1/00.182539
2/00.219032
3/00.264227
4/00.319722
250 kcmil0.390418
300 kcmil0.453615
350 kcmil0.516614
400 kcmil0.578212
500 kcmil0.698410
600 kcmil0.87098
700 kcmil0.99237
750 kcmil1.05326
800 kcmil1.11226
900 kcmil1.23515
1000 kcmil1.35195
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 5" PVC Schedule 80 with 12 AWG THHN: 17.855 × 0.40 ÷ 0.0133 = 536.99 → 537 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 5" PVC Schedule 80 that raises the usable area from 7.142 in² to 10.713 in².

Other PVC Schedule 80 Sizes

5" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 5-inch PVC Schedule 80 conduit?

A 5-inch PVC Schedule 80 conduit has 17.855 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 7.142 in². That works out to 537 #12 THHN, 736 #14 THHN, 338 #10 THHN, or 195 #8 THHN conductors.

How many 12 AWG THHN wires fit in 5-inch PVC Schedule 80?

537 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 5-inch PVC Schedule 80 is 7.142 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.