5" Rigid Metal (RMC) Conduit Fill Chart

14 AWG THHN
833
conductors max
12 AWG THHN
608
conductors max
10 AWG THHN
383
conductors max
Usable area at 40% fill: 8.085 in² · NEC Chapter 9, Tables 1, 4 and 5

About Rigid Metal (RMC) (Rigid Metal Conduit (RMC))

Threaded heavy-wall galvanized steel (or aluminum) conduit. The most protective raceway; used for services, hazardous locations and anywhere subject to severe physical damage. Trade size 5" is covered by NEC Article 344, and its internal dimensions come from NEC Chapter 9, Table 4.

5" Rigid Metal (RMC) — Internal Area & Fill Limits

Trade size5"
Total internal area (100%)20.212 in²
1 conductor (53%)10.712 in²
2 conductors (31%)6.266 in²
Over 2 conductors (40%)8.085 in²

5" Rigid Metal (RMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097833
120.0133608
100.0211383
80.0366221
60.0507159
40.082498
30.097383
20.115870
10.156251
1/00.185543
2/00.222336
3/00.267930
4/00.323725
250 kcmil0.397020
300 kcmil0.460817
350 kcmil0.524215
400 kcmil0.586313
500 kcmil0.707311
600 kcmil0.86769
700 kcmil0.98878
750 kcmil1.04967
800 kcmil1.10857
900 kcmil1.23116
1000 kcmil1.34786
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

5" Rigid Metal (RMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139581
120.0181446
100.0243332
80.0437185
60.0590137
40.081499
30.096284
20.114670
10.153452
1/00.182544
2/00.219037
3/00.264230
4/00.319725
250 kcmil0.390420
300 kcmil0.453618
350 kcmil0.516615
400 kcmil0.578214
500 kcmil0.698411
600 kcmil0.87099
700 kcmil0.99238
750 kcmil1.05327
800 kcmil1.11227
900 kcmil1.23516
1000 kcmil1.35196
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 5" Rigid Metal (RMC) with 12 AWG THHN: 20.212 × 0.40 ÷ 0.0133 = 607.88 → 608 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 5" Rigid Metal (RMC) that raises the usable area from 8.085 in² to 12.127 in².

Other Rigid Metal (RMC) Sizes

5" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 5-inch Rigid Metal Conduit conduit?

A 5-inch Rigid Metal Conduit conduit has 20.212 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 8.085 in². That works out to 608 #12 THHN, 833 #14 THHN, 383 #10 THHN, or 221 #8 THHN conductors.

How many 12 AWG THHN wires fit in 5-inch Rigid Metal Conduit?

608 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 5-inch Rigid Metal Conduit is 8.085 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.