6" Rigid Metal (RMC) Conduit Fill Chart

14 AWG THHN
1202
conductors max
12 AWG THHN
877
conductors max
10 AWG THHN
552
conductors max
Usable area at 40% fill: 11.663 in² · NEC Chapter 9, Tables 1, 4 and 5

About Rigid Metal (RMC) (Rigid Metal Conduit (RMC))

Threaded heavy-wall galvanized steel (or aluminum) conduit. The most protective raceway; used for services, hazardous locations and anywhere subject to severe physical damage. Trade size 6" is covered by NEC Article 344, and its internal dimensions come from NEC Chapter 9, Table 4.

6" Rigid Metal (RMC) — Internal Area & Fill Limits

Trade size6"
Total internal area (100%)29.158 in²
1 conductor (53%)15.454 in²
2 conductors (31%)9.039 in²
Over 2 conductors (40%)11.663 in²

6" Rigid Metal (RMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.00971202
120.0133877
100.0211552
80.0366318
60.0507230
40.0824141
30.0973120
20.1158100
10.156274
1/00.185563
2/00.222352
3/00.267943
4/00.323736
250 kcmil0.397029
300 kcmil0.460825
350 kcmil0.524222
400 kcmil0.586320
500 kcmil0.707316
600 kcmil0.867613
700 kcmil0.988711
750 kcmil1.049611
800 kcmil1.108510
900 kcmil1.23119
1000 kcmil1.34788
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

6" Rigid Metal (RMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139839
120.0181644
100.0243480
80.0437267
60.0590197
40.0814143
30.0962121
20.1146101
10.153476
1/00.182564
2/00.219053
3/00.264244
4/00.319736
250 kcmil0.390430
300 kcmil0.453625
350 kcmil0.516622
400 kcmil0.578220
500 kcmil0.698416
600 kcmil0.870913
700 kcmil0.992311
750 kcmil1.053211
800 kcmil1.112210
900 kcmil1.23519
1000 kcmil1.35198
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 6" Rigid Metal (RMC) with 12 AWG THHN: 29.158 × 0.40 ÷ 0.0133 = 876.93 → 877 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 6" Rigid Metal (RMC) that raises the usable area from 11.663 in² to 17.495 in².

Other Rigid Metal (RMC) Sizes

6" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 6-inch Rigid Metal Conduit conduit?

A 6-inch Rigid Metal Conduit conduit has 29.158 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 11.663 in². That works out to 877 #12 THHN, 1202 #14 THHN, 552 #10 THHN, or 318 #8 THHN conductors.

How many 12 AWG THHN wires fit in 6-inch Rigid Metal Conduit?

877 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 6-inch Rigid Metal Conduit is 11.663 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.