6" PVC Schedule 40 Conduit Fill Chart

14 AWG THHN
1178
conductors max
12 AWG THHN
859
conductors max
10 AWG THHN
541
conductors max
Usable area at 40% fill: 11.427 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Schedule 40 (Rigid PVC Conduit, Schedule 40)

Gray nonmetallic conduit for underground runs, slabs and wet or corrosive locations. Needs a separate equipment grounding conductor, which counts toward fill. Trade size 6" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

6" PVC Schedule 40 — Internal Area & Fill Limits

Trade size6"
Total internal area (100%)28.567 in²
1 conductor (53%)15.141 in²
2 conductors (31%)8.856 in²
Over 2 conductors (40%)11.427 in²

6" PVC Schedule 40 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.00971178
120.0133859
100.0211541
80.0366312
60.0507225
40.0824138
30.0973117
20.115898
10.156273
1/00.185561
2/00.222351
3/00.267942
4/00.323735
250 kcmil0.397028
300 kcmil0.460824
350 kcmil0.524221
400 kcmil0.586319
500 kcmil0.707316
600 kcmil0.867613
700 kcmil0.988711
750 kcmil1.049611
800 kcmil1.108510
900 kcmil1.23119
1000 kcmil1.34788
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

6" PVC Schedule 40 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139822
120.0181631
100.0243470
80.0437261
60.0590193
40.0814140
30.0962118
20.114699
10.153474
1/00.182562
2/00.219052
3/00.264243
4/00.319735
250 kcmil0.390429
300 kcmil0.453625
350 kcmil0.516622
400 kcmil0.578219
500 kcmil0.698416
600 kcmil0.870913
700 kcmil0.992311
750 kcmil1.053211
800 kcmil1.112210
900 kcmil1.23519
1000 kcmil1.35198
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 6" PVC Schedule 40 with 12 AWG THHN: 28.567 × 0.40 ÷ 0.0133 = 859.16 → 859 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 6" PVC Schedule 40 that raises the usable area from 11.427 in² to 17.14 in².

Other PVC Schedule 40 Sizes

6" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 6-inch PVC Schedule 40 conduit?

A 6-inch PVC Schedule 40 conduit has 28.567 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 11.427 in². That works out to 859 #12 THHN, 1178 #14 THHN, 541 #10 THHN, or 312 #8 THHN conductors.

How many 12 AWG THHN wires fit in 6-inch PVC Schedule 40?

859 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 6-inch PVC Schedule 40 is 11.427 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.