5" PVC Schedule 40 Conduit Fill Chart

14 AWG THHN
815
conductors max
12 AWG THHN
594
conductors max
10 AWG THHN
374
conductors max
Usable area at 40% fill: 7.904 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Schedule 40 (Rigid PVC Conduit, Schedule 40)

Gray nonmetallic conduit for underground runs, slabs and wet or corrosive locations. Needs a separate equipment grounding conductor, which counts toward fill. Trade size 5" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

5" PVC Schedule 40 — Internal Area & Fill Limits

Trade size5"
Total internal area (100%)19.761 in²
1 conductor (53%)10.473 in²
2 conductors (31%)6.126 in²
Over 2 conductors (40%)7.904 in²

5" PVC Schedule 40 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097815
120.0133594
100.0211374
80.0366216
60.0507156
40.082496
30.097381
20.115868
10.156250
1/00.185542
2/00.222335
3/00.267929
4/00.323724
250 kcmil0.397020
300 kcmil0.460817
350 kcmil0.524215
400 kcmil0.586313
500 kcmil0.707311
600 kcmil0.86769
700 kcmil0.98878
750 kcmil1.04967
800 kcmil1.10857
900 kcmil1.23116
1000 kcmil1.34786
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

5" PVC Schedule 40 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139568
120.0181436
100.0243325
80.0437181
60.0590134
40.081497
30.096282
20.114669
10.153451
1/00.182543
2/00.219036
3/00.264230
4/00.319724
250 kcmil0.390420
300 kcmil0.453617
350 kcmil0.516615
400 kcmil0.578213
500 kcmil0.698411
600 kcmil0.87099
700 kcmil0.99238
750 kcmil1.05327
800 kcmil1.11227
900 kcmil1.23516
1000 kcmil1.35196
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 5" PVC Schedule 40 with 12 AWG THHN: 19.761 × 0.40 ÷ 0.0133 = 594.32 → 594 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 5" PVC Schedule 40 that raises the usable area from 7.904 in² to 11.857 in².

Other PVC Schedule 40 Sizes

5" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 5-inch PVC Schedule 40 conduit?

A 5-inch PVC Schedule 40 conduit has 19.761 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 7.904 in². That works out to 594 #12 THHN, 815 #14 THHN, 374 #10 THHN, or 216 #8 THHN conductors.

How many 12 AWG THHN wires fit in 5-inch PVC Schedule 40?

594 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 5-inch PVC Schedule 40 is 7.904 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.