Gray nonmetallic conduit for underground runs, slabs and wet or corrosive locations. Needs a separate equipment grounding conductor, which counts toward fill. Trade size 5" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.
| Trade size | 5" |
| Total internal area (100%) | 19.761 in² |
| 1 conductor (53%) | 10.473 in² |
| 2 conductors (31%) | 6.126 in² |
| Over 2 conductors (40%) | 7.904 in² |
| Wire size | Area (in²) | Max conductors |
|---|---|---|
| 14 | 0.0097 | 815 |
| 12 | 0.0133 | 594 |
| 10 | 0.0211 | 374 |
| 8 | 0.0366 | 216 |
| 6 | 0.0507 | 156 |
| 4 | 0.0824 | 96 |
| 3 | 0.0973 | 81 |
| 2 | 0.1158 | 68 |
| 1 | 0.1562 | 50 |
| 1/0 | 0.1855 | 42 |
| 2/0 | 0.2223 | 35 |
| 3/0 | 0.2679 | 29 |
| 4/0 | 0.3237 | 24 |
| 250 kcmil | 0.3970 | 20 |
| 300 kcmil | 0.4608 | 17 |
| 350 kcmil | 0.5242 | 15 |
| 400 kcmil | 0.5863 | 13 |
| 500 kcmil | 0.7073 | 11 |
| 600 kcmil | 0.8676 | 9 |
| 700 kcmil | 0.9887 | 8 |
| 750 kcmil | 1.0496 | 7 |
| 800 kcmil | 1.1085 | 7 |
| 900 kcmil | 1.2311 | 6 |
| 1000 kcmil | 1.3478 | 6 |
| Wire size | Area (in²) | Max conductors |
|---|---|---|
| 14 | 0.0139 | 568 |
| 12 | 0.0181 | 436 |
| 10 | 0.0243 | 325 |
| 8 | 0.0437 | 181 |
| 6 | 0.0590 | 134 |
| 4 | 0.0814 | 97 |
| 3 | 0.0962 | 82 |
| 2 | 0.1146 | 69 |
| 1 | 0.1534 | 51 |
| 1/0 | 0.1825 | 43 |
| 2/0 | 0.2190 | 36 |
| 3/0 | 0.2642 | 30 |
| 4/0 | 0.3197 | 24 |
| 250 kcmil | 0.3904 | 20 |
| 300 kcmil | 0.4536 | 17 |
| 350 kcmil | 0.5166 | 15 |
| 400 kcmil | 0.5782 | 13 |
| 500 kcmil | 0.6984 | 11 |
| 600 kcmil | 0.8709 | 9 |
| 700 kcmil | 0.9923 | 8 |
| 750 kcmil | 1.0532 | 7 |
| 800 kcmil | 1.1122 | 7 |
| 900 kcmil | 1.2351 | 6 |
| 1000 kcmil | 1.3519 | 6 |
Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.
Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)
For 5" PVC Schedule 40 with 12 AWG THHN: 19.761 × 0.40 ÷ 0.0133 = 594.32 → 594 conductors
Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 5" PVC Schedule 40 that raises the usable area from 7.904 in² to 11.857 in².
A 5-inch PVC Schedule 40 conduit has 19.761 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 7.904 in². That works out to 594 #12 THHN, 815 #14 THHN, 374 #10 THHN, or 216 #8 THHN conductors.
594 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 5-inch PVC Schedule 40 is 7.904 in².
NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.