WireSizing
Wire gauge reference & calculator

1000 kcmil Wire

1000 kcmil conductor specifications: 1,000,000 circular mils (506.7 mm²), 545A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.

Area
506.7 mm²
1,000,000 cmil
Ampacity (Cu)
545A
75°C — Table 310.16
Ampacity (Al)
445A
75°C — Table 310.16
Resistance (Cu)
0.0129
Ω/1000 ft at 75°C

1000 kcmil Ampacity (Table 310.16)

Material 60°C 75°C 90°C
Copper455545615
Aluminum375445500
30°C ambient, not more than three current-carrying conductors in raceway, cable or earth.

1000 kcmil Free-Air Ampacity (Table 310.17)

Material 60°C 75°C 90°C
Copper7809351055
Aluminum625750845
Single conductor in free air, 30°C ambient.

1000 kcmil Conduit Fill (THHN, 40%)

1000 kcmil Insulated Conductor Dimensions

Insulation Diameter (in) Area (in²)
THHN / THWN-21.3171.3478
XHHW / XHHW-21.3121.3519
THW / THHW1.3721.4784
RHH / RHW-21.5021.7719

1000 kcmil Voltage Drop (3%, copper)

Load 120V 1ϕ 240V 1ϕ 208V 3ϕ 480V 3ϕ
100 A1395 ft2790 ft2792 ft6444 ft
150 A930 ft1860 ft1861 ft4296 ft
200 A697 ft1395 ft1396 ft3222 ft
250 A558 ft1116 ft1117 ft2577 ft
300 A465 ft930 ft930 ft2148 ft
Maximum one-way distances. Based on 0.0129 Ω/1000 ft (stranded copper at 75°C, NEC Chapter 9 Table 8).
← 900 kcmil

Frequently Asked Questions

How many amps can 1000 kcmil wire carry?

1000 kcmil copper is rated 455 A at 60°C, 545 A at 75°C and 615 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 375, 445 and 500 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.

What size conduit do I need for 1000 kcmil wire?

Three 1000 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.

What is the diameter of 1000 kcmil wire?

The bare conductor is 1,000,000 circular mils (506.7 mm²). With THHN insulation the overall diameter is about 1.317 in and the area is 1.3478 in².

Explore

Conduit fill charts → Ampacity tables → Full AWG chart → Wire size calculator →

WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.