1000 kcmil conductor specifications: 1,000,000 circular mils (506.7 mm²), 545A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 455 | 545 | 615 |
| Aluminum | 375 | 445 | 500 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 780 | 935 | 1055 |
| Aluminum | 625 | 750 | 845 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 1.317 | 1.3478 |
| XHHW / XHHW-2 | 1.312 | 1.3519 |
| THW / THHW | 1.372 | 1.4784 |
| RHH / RHW-2 | 1.502 | 1.7719 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 1395 ft | 2790 ft | 2792 ft | 6444 ft |
| 150 A | 930 ft | 1860 ft | 1861 ft | 4296 ft |
| 200 A | 697 ft | 1395 ft | 1396 ft | 3222 ft |
| 250 A | 558 ft | 1116 ft | 1117 ft | 2577 ft |
| 300 A | 465 ft | 930 ft | 930 ft | 2148 ft |
1000 kcmil copper is rated 455 A at 60°C, 545 A at 75°C and 615 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 375, 445 and 500 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 1000 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 1,000,000 circular mils (506.7 mm²). With THHN insulation the overall diameter is about 1.317 in and the area is 1.3478 in².
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.