900 kcmil conductor specifications: 900,000 circular mils (456.03 mm²), 520A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 435 | 520 | 585 |
| Aluminum | 355 | 425 | 480 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 730 | 870 | 980 |
| Aluminum | 580 | 700 | 790 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 1.252 | 1.2311 |
| XHHW / XHHW-2 | 1.254 | 1.2351 |
| THW / THHW | 1.314 | 1.3561 |
| RHH / RHW-2 | 1.444 | 1.6377 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 1258 ft | 2517 ft | 2519 ft | 5813 ft |
| 150 A | 839 ft | 1678 ft | 1679 ft | 3875 ft |
| 200 A | 629 ft | 1258 ft | 1259 ft | 2906 ft |
| 250 A | 503 ft | 1006 ft | 1007 ft | 2325 ft |
| 300 A | 419 ft | 839 ft | 839 ft | 1937 ft |
900 kcmil copper is rated 435 A at 60°C, 520 A at 75°C and 585 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 355, 425 and 480 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 900 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 900,000 circular mils (456.03 mm²). With THHN insulation the overall diameter is about 1.252 in and the area is 1.2311 in².
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.