800 kcmil conductor specifications: 800,000 circular mils (405.36 mm²), 490A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 410 | 490 | 555 |
| Aluminum | 330 | 395 | 445 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 680 | 815 | 920 |
| Aluminum | 535 | 645 | 725 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 1.188 | 1.1085 |
| XHHW / XHHW-2 | 1.19 | 1.1122 |
| THW / THHW | 1.25 | 1.2272 |
| RHH / RHW-2 | 1.38 | 1.4957 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 1118 ft | 2236 ft | 2237 ft | 5163 ft |
| 150 A | 745 ft | 1490 ft | 1491 ft | 3442 ft |
| 200 A | 559 ft | 1118 ft | 1118 ft | 2581 ft |
| 250 A | 447 ft | 894 ft | 895 ft | 2065 ft |
| 300 A | 372 ft | 745 ft | 745 ft | 1721 ft |
800 kcmil copper is rated 410 A at 60°C, 490 A at 75°C and 555 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 330, 395 and 445 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 800 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 800,000 circular mils (405.36 mm²). With THHN insulation the overall diameter is about 1.188 in and the area is 1.1085 in².