750 kcmil conductor specifications: 750,000 circular mils (380.03 mm²), 475A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 400 | 475 | 535 |
| Aluminum | 320 | 385 | 435 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 655 | 785 | 885 |
| Aluminum | 515 | 620 | 700 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 1.156 | 1.0496 |
| XHHW / XHHW-2 | 1.158 | 1.0532 |
| THW / THHW | 1.218 | 1.1652 |
| RHH / RHW-2 | 1.348 | 1.4272 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 1052 ft | 2105 ft | 2106 ft | 4861 ft |
| 150 A | 701 ft | 1403 ft | 1404 ft | 3241 ft |
| 200 A | 526 ft | 1052 ft | 1053 ft | 2430 ft |
| 250 A | 421 ft | 842 ft | 842 ft | 1944 ft |
| 300 A | 350 ft | 701 ft | 702 ft | 1620 ft |
750 kcmil copper is rated 400 A at 60°C, 475 A at 75°C and 535 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 320, 385 and 435 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 750 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 750,000 circular mils (380.03 mm²). With THHN insulation the overall diameter is about 1.156 in and the area is 1.0496 in².
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.