700 kcmil conductor specifications: 700,000 circular mils (354.69 mm²), 460A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 385 | 460 | 520 |
| Aluminum | 315 | 375 | 425 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 630 | 755 | 850 |
| Aluminum | 500 | 595 | 670 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 1.122 | 0.9887 |
| XHHW / XHHW-2 | 1.124 | 0.9923 |
| THW / THHW | 1.184 | 1.101 |
| RHH / RHW-2 | 1.314 | 1.3561 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 978 ft | 1956 ft | 1957 ft | 4518 ft |
| 150 A | 652 ft | 1304 ft | 1305 ft | 3012 ft |
| 200 A | 489 ft | 978 ft | 978 ft | 2259 ft |
| 250 A | 391 ft | 782 ft | 783 ft | 1807 ft |
| 300 A | 326 ft | 652 ft | 652 ft | 1506 ft |
700 kcmil copper is rated 385 A at 60°C, 460 A at 75°C and 520 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 315, 375 and 425 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 700 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 700,000 circular mils (354.69 mm²). With THHN insulation the overall diameter is about 1.122 in and the area is 0.9887 in².
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.