600 kcmil conductor specifications: 600,000 circular mils (304.02 mm²), 420A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 350 | 420 | 475 |
| Aluminum | 285 | 340 | 385 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 575 | 690 | 780 |
| Aluminum | 455 | 545 | 615 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 1.051 | 0.8676 |
| XHHW / XHHW-2 | 1.053 | 0.8709 |
| THW / THHW | 1.113 | 0.9729 |
| RHH / RHW-2 | 1.243 | 1.2135 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 841 ft | 1682 ft | 1683 ft | 3884 ft |
| 150 A | 560 ft | 1121 ft | 1122 ft | 2589 ft |
| 200 A | 420 ft | 841 ft | 841 ft | 1942 ft |
| 250 A | 336 ft | 672 ft | 673 ft | 1553 ft |
| 300 A | 280 ft | 560 ft | 561 ft | 1294 ft |
600 kcmil copper is rated 350 A at 60°C, 420 A at 75°C and 475 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 285, 340 and 385 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 600 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 600,000 circular mils (304.02 mm²). With THHN insulation the overall diameter is about 1.051 in and the area is 0.8676 in².