500 kcmil conductor specifications: 500,000 circular mils (253.35 mm²), 380A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 320 | 380 | 430 |
| Aluminum | 260 | 310 | 350 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 515 | 620 | 700 |
| Aluminum | 405 | 485 | 545 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 0.949 | 0.7073 |
| XHHW / XHHW-2 | 0.943 | 0.6984 |
| THW / THHW | 1.003 | 0.7901 |
| RHH / RHW-2 | 1.133 | 1.0082 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 697 ft | 1395 ft | 1396 ft | 3222 ft |
| 150 A | 465 ft | 930 ft | 930 ft | 2148 ft |
| 200 A | 348 ft | 697 ft | 698 ft | 1611 ft |
| 250 A | 279 ft | 558 ft | 558 ft | 1288 ft |
| 300 A | 232 ft | 465 ft | 465 ft | 1074 ft |
500 kcmil copper is rated 320 A at 60°C, 380 A at 75°C and 430 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 260, 310 and 350 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 500 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 500,000 circular mils (253.35 mm²). With THHN insulation the overall diameter is about 0.949 in and the area is 0.7073 in².
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.