400 kcmil conductor specifications: 400,000 circular mils (202.68 mm²), 335A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 280 | 335 | 380 |
| Aluminum | 225 | 270 | 305 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 455 | 545 | 615 |
| Aluminum | 355 | 425 | 480 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 0.864 | 0.5863 |
| XHHW / XHHW-2 | 0.858 | 0.5782 |
| THW / THHW | 0.918 | 0.6619 |
| RHH / RHW-2 | 1.048 | 0.8626 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 560 ft | 1121 ft | 1122 ft | 2589 ft |
| 150 A | 373 ft | 747 ft | 748 ft | 1726 ft |
| 200 A | 280 ft | 560 ft | 561 ft | 1294 ft |
| 250 A | 224 ft | 448 ft | 448 ft | 1035 ft |
| 300 A | 186 ft | 373 ft | 374 ft | 863 ft |
400 kcmil copper is rated 280 A at 60°C, 335 A at 75°C and 380 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 225, 270 and 305 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 400 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 400,000 circular mils (202.68 mm²). With THHN insulation the overall diameter is about 0.864 in and the area is 0.5863 in².