350 kcmil conductor specifications: 350,000 circular mils (177.34 mm²), 310A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 260 | 310 | 350 |
| Aluminum | 210 | 250 | 280 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 420 | 505 | 570 |
| Aluminum | 330 | 395 | 445 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 0.817 | 0.5242 |
| XHHW / XHHW-2 | 0.811 | 0.5166 |
| THW / THHW | 0.871 | 0.5958 |
| RHH / RHW-2 | 1.001 | 0.787 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 490 ft | 980 ft | 981 ft | 2265 ft |
| 150 A | 326 ft | 653 ft | 654 ft | 1510 ft |
| 200 A | 245 ft | 490 ft | 490 ft | 1132 ft |
| 250 A | 196 ft | 392 ft | 392 ft | 906 ft |
| 300 A | 163 ft | 326 ft | 327 ft | 755 ft |
350 kcmil copper is rated 260 A at 60°C, 310 A at 75°C and 350 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 210, 250 and 280 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 350 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 350,000 circular mils (177.34 mm²). With THHN insulation the overall diameter is about 0.817 in and the area is 0.5242 in².
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.