300 kcmil conductor specifications: 300,000 circular mils (152.01 mm²), 285A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 240 | 285 | 320 |
| Aluminum | 195 | 230 | 260 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 375 | 445 | 500 |
| Aluminum | 290 | 350 | 395 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 0.766 | 0.4608 |
| XHHW / XHHW-2 | 0.76 | 0.4536 |
| THW / THHW | 0.82 | 0.5281 |
| RHH / RHW-2 | 0.95 | 0.7088 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 419 ft | 839 ft | 839 ft | 1937 ft |
| 150 A | 279 ft | 559 ft | 559 ft | 1291 ft |
| 200 A | 209 ft | 419 ft | 419 ft | 968 ft |
| 250 A | 167 ft | 335 ft | 335 ft | 775 ft |
| 300 A | 139 ft | 279 ft | 279 ft | 645 ft |
300 kcmil copper is rated 240 A at 60°C, 285 A at 75°C and 320 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 195, 230 and 260 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 300 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 300,000 circular mils (152.01 mm²). With THHN insulation the overall diameter is about 0.766 in and the area is 0.4608 in².