250 kcmil conductor specifications: 250,000 circular mils (126.67 mm²), 255A ampacity (copper, 75°C). Conduit fill, resistance and voltage-drop data.
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 215 | 255 | 290 |
| Aluminum | 170 | 205 | 230 |
| Material | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 340 | 405 | 455 |
| Aluminum | 265 | 315 | 355 |
| Insulation | Diameter (in) | Area (in²) |
|---|---|---|
| THHN / THWN-2 | 0.711 | 0.397 |
| XHHW / XHHW-2 | 0.705 | 0.3904 |
| THW / THHW | 0.765 | 0.4596 |
| RHH / RHW-2 | 0.895 | 0.6291 |
| Load | 120V 1ϕ | 240V 1ϕ | 208V 3ϕ | 480V 3ϕ |
|---|---|---|---|---|
| 100 A | 349 ft | 699 ft | 699 ft | 1614 ft |
| 150 A | 233 ft | 466 ft | 466 ft | 1076 ft |
| 200 A | 174 ft | 349 ft | 349 ft | 807 ft |
| 250 A | 139 ft | 279 ft | 279 ft | 645 ft |
| 300 A | 116 ft | 233 ft | 233 ft | 538 ft |
250 kcmil copper is rated 215 A at 60°C, 255 A at 75°C and 290 A at 90°C in conduit or cable (Table 310.16). Aluminum is rated 170, 205 and 230 A. Most terminations are 75°C-rated, so the 75°C figure is normally used.
Three 250 kcmil THHN conductors need at least the conduit size shown in the fill table above. Add the ground wire’s area for the actual installation.
The bare conductor is 250,000 circular mils (126.67 mm²). With THHN insulation the overall diameter is about 0.711 in and the area is 0.397 in².